- Products
- Residual current monitoring

LINETRAXX® RCMS490-D
- As an alternative to the insulation test by means of periodic verification. For MRCD applications in combination with a circuit breaker
- Alternating, pulsating or AC/DC sensitive measurements can optionally be carried out by selecting the measuring current transformer for each channel
- Device version RCMS490 with one alarm contact per channel
- Analysis of the harmonics, DC, THF
- Adjustable frequency response for protection of persons, fire protection, plant protection
The RCMS system consists of one or more RCMS460-D/-L or RCMS490-D/-L residual current monitors, which are able to detect and evaluate fault, residual and operating currents in earthed power supplies via the related measuring current transformers. The maximum voltage of the system to be monitored depends on the nominal insulation voltage of the measuring current transformer used in the case of busbar systems, resp. depend on the cables or conductors that are routed through.
Closed CTUB100 series measuring current transformers are required to measure AC/DC sensitive residual currents (according to IEC/TR 60755: Type B). For the CTUB100 series measuring current transformers require one 24 V DC power supply unit (e.g. STEP-PS series). CTAC… (closed), WR… (rectangular), WS… (split-core) and WF… (flexible) series measuring current transformers are used for alternating and pulsating currents (according to IEC/TR 60755: Type A).
Any combination of the various measuring current transformer series can be connected to the monitor measuring channels. Each RCMS460-D/-L and RCMS490-D/-L has 12 measuring channels. Up to 90 residual current monitors can be connected via a BMS bus (RS-485 interface with BMS protocol), thereby up to 1080 measuring channels (sub-circuits) can be monitored.
If this product is to be used for personnel, fire or plant protection, the frequency response can be set accordingly. The measured currents can be analysed for harmonics.
- Features
- Applications
- Accessories
- Ordering information
- Downloads
- Optional AC, pulsed DC or AC/DC sensitive measurement by selecting the respective measuring current transformer for each channel
- True r.m.s. value measurement
- 12 measuring channels per device for residual current measurement or digital input
- Up to 90 RCMS… monitors, up to1080 measuring channels in the system
- Fast parallel scanning for all channels
- Response ranges: 10 mA…10 A (0…2000 Hz), 6 mA…20 A (42…2000 Hz), 100 mA…125 A (42…2000 Hz) RCMS…-D4
- Preset function
- Adjustable time delays
- The frequency response characteristics can be set for the protection of persons, fire and plant protection
- History memory with date and time stamp for 300 data records
- Data logger for 300 data records/channel
- Analysis of the harmonics, DC, THD
- Two alarm relays with one changeover contact each
- Device version RCMS490 with one alarm contact per channel
- N/O or N/C operation and fault memory selectable
- Connection external test/reset button
- Backlit graphical display (7-segment display) and alarm LEDs
- Data exchange via BMS bus
- Password protection for device setting
- Continuous CT connection monitoring
- RoHS compliant
- Measuring and evaluating residual, fault and rated currents of loads and installations in the frequency range of 0…2000 Hz (CTUB100 series measuring current transformers), 42…2000 Hz (CTAC…, WR…, WS…, WF… series measuring current transformers).
- Monitoring of currents regarded as fire hazards in flammable atmospheres
- EMC monitoring of TN-S systems for “stray currents” and additional N-PE connections.
- Monitoring of N conductors for overload caused by harmonics
- Monitoring of PE and equipotential bonding conductors to ensure they are free of current
- Residual current monitoring of stationary electrical equipment and systems to determine test intervals which meet practical requirements in compliance with the accident prevention regulations DGUV V3 (Germany).
- Personnel and fire protection due to rapid disconnection
- Monitoring of digital inputs
Optional accessories for LINETRAXX® RCMS490-D
Type | Art. No. |
---|---|
STEP-PS/1 AC/24 DC/0.5 (Power supply unit for supplying up to 4 CTUB100 series measuring current transformers) | B94053110 |
STEP-PS/1 AC/24 DC/1.75 (Power supply unit for supplying up to 14 CTUB100 series measuring current transformers) | B94053111 |
STEP-PS/1 AC/24 DC/4.2 (Power supply unit for supplying up to 34 CTUB100 series measuring current transformers) | B94053112 |
DI-1PSM (RS-485 repeater) | B95012044 |
Repeaters and interface converters
Type | Description | Supply voltage US* | Art. No. |
---|---|---|---|
COM465IP | Condition Monitor with integrated gateway: Bender system/Ethernet | AC/DC 24…240 V, DC, 50…60 Hz | B95061065 |
COM465IP-24 V | Condition Monitor with integrated gateway: Bender system/Ethernet | DC 24 V | B95061066 |
COM465IP Function package A | Individual text messages for all devices/channels, device failure monitoring, email in the event of an alarm | -- | B75061011 |
COM465IP Function package B | Modbus TCP server for max. 98 * 139 BMS nodes as well as BCOM and universal measuring devices, SNMP server | -- | B75061012 |
COM465IP Function package C | Parameter setting of BMS devices as well as BCOM and universal measuring devices | -- | B75061013 |
COM465IP Function package D | Visualisation of Bender systems, System visualisation | -- | B75061014 |
COM465IP Function package E | Virtual devices | -- | B75061015 |
COM465IP Function package F | Integration of third-party devices | -- | B75061016 |
CP700 | Condition Monitor for the connection of Bender BMS devices and universal measuring devices to TCP/IP networks | -- | B95061030 |
COM462RTU | BMS Modbus RTU gateway | AC/DC 76…276 V */ AC 42…460 Hz/DC | B95061022 |
Alarm indicator and test combination
Type | Art. No. |
---|---|
MK800A-11 | B95100102 |
MK800A-12 | B95100103 |
MK2430-11 | B95100001 |
MK2430-12 | B95100002 |
MK2430P-11 | B95100003 |
MK2430P-12 | B95100004 |
MK2430A-11 | B95100005 |
MK2430A-12 | B95100006 |
MK2430PA-11 | B95100007 |
MK2430PA-12 | B95100008 |
MK2430S-11 | B95100011 |
MK2430S-12 | B95100012 |
Pulsating current sensitive measuring current transformers for RCMS460/490
Type | Internal diameter/mm | Type of construction | Art. No. |
---|---|---|---|
CTAC20 | ø 20 | circular | B98110005 |
CTAC35 | ø 35 | circular | B98110007 |
CTAC60 | ø 60 | circular | B98110017 |
CTAC120 | ø 120 | circular | B98110019 |
CTAC210 | ø 210 | circular | B98110020 |
WR70x175S | 70 x 175 | rectangular | B11738 |
WR70x175SP | 70 x 175 | rectangular | B11790 |
WR115x305S | 115 x 305 | rectangular | B11739 |
WR115x305SP | 115 x 305 | rectangular | B11791 |
WR150x350S | 150 x 350 | rectangular | B911740 |
WR150x350SP | 150 x 350 | rectangular | B911792 |
WR200x500S | 200 x 500 | rectangular | B911763 |
WR200x500SP | 200 x 500 | rectangular | B911793 |
WS20x30 | 20 x 30 | split-core | B98080601 |
WS50x80 | 50 x 80 | split-core | B98080603 |
WS80x120 | 80 x 120 | split-core | B98080606 |
AC/DC sensitive measuring current transformers for RCMS460/490
Type | Internal diameter/mm | Type of construction | Art. No. |
---|---|---|---|
CTUB102-CTBC20 | ø 20 | circular | B78120011 |
CTUB102-CTBC20P | ø 20 | circular | B78120021 |
CTUB102-CTBC35 | ø 35 | circular | B78120013 |
CTUB102-CTBC35P | ø 35 | circular | B78120023 |
CTUB102-CTBC60 | ø 60 | circular | B78120015 |
CTUB102-CTBC60P | ø 60 | circular | B78120025 |
CTUB102-CTBC120 | ø 120 | circular | B78120017 |
CTUB102-CTBC120P | ø 120 | circular | B78120027 |
CTUB102-CTBC210 | ø 210 | circular | B78120019 |
CTUB102-CTBC210P | ø 210 | circular | B78120029 |
Connection cable for CTUB100 series measuring current transformers
Type | Length/m | Art. No. |
---|---|---|
CTXS-100 | 1 | B98110090 |
CTXS-250 | 2,5 | B98110091 |
CTXS-500 | 5 | B98110092 |
CTXS-1000 | 10 | B98110093 |
Flexible measuring current transformers (pulsed DC sensitive) for RCMS460/490
Type | Internal diameter/mm | Supply voltage US | Art. No. |
---|---|---|---|
WF170-1 | 170 | DC 9,6…94 V / AC 16…72 V, 42…460 Hz | B78080201 |
WF170-2 | 170 | DC 70…300 V / AC 70…300 V, 42…460 Hz | B78080202 |
WF250-1 | 250 | DC 9,6…94 V / AC 16…72 V, 42…460 Hz | B78080203 |
WF250-2 | 250 | DC 70…300 V / AC 70…300 V, 42…460 Hz | B78080204 |
WF500-1 | 500 | DC 9,6…94 V / AC 16…72 V, 42…460 Hz | B78080205 |
WF500-2 | 500 | DC 70…300 V / AC 70…300 V, 42…460 Hz | B78080206 |
WF800-1 | 800 | DC 9,6…94 V / AC 16…72 V, 42…460 Hz | B78080207 |
WF800-2 | 800 | DC 70…300 V / AC 70…300 V, 42…460 Hz | B78080208 |
WF1200-1 | 1200 | DC 9,6…94 V / AC 16…72 V, 42…460 Hz | B78080209 |
WF1200-2 | 1200 | DC 70…300 V / AC 70…300 V, 42…460 Hz | B78080210 |
Accessories
Type | Art. No. |
---|---|
Mounting clip for enclosure XM420 (1 piece per device) | B98060008 |
XM460 mounting frame | B990995 |
XM490 mounting frame | B990996 |
Variants of LINETRAXX® RCMS490-D
Type | Supply voltage US* | Art. No. |
---|---|---|
RCMS490-D-1 | DC 16…94 V / AC 16…72 V, 42…460 Hz | B94053005 |
RCMS490-D4-1 | DC 16…94 V / AC 16…72 V, 42…460 Hz | B94053011 |
RCMS490-D-2 | DC 70…276 V / AC 70…276 V, 42…460 Hz | B94053006 |
RCMS490-D4-2 | DC 70…276 V / AC 70…276 V, 42…460 Hz | B94053012 |
Downloads for LINETRAXX® RCMS490-D