- Products
- Residual current monitoring

LINETRAXX® RCMA420
The AC/DC sensitive residual current monitor RCMA420 is designed for monitoring earthed power supply systems (TN and TT systems) where smooth DC fault currents or residual currents continuously greater than zero may occur. These are in particular loads containing six-pulse rectifiers or one way rectifiers with smoothing, such as converters, battery chargers, construction site equipment with frequency-controlled drives. Currents in single conductors can be monitored too.
The prewarning stage (50…100 % of the set response value IΔn2) allow to distinguish between prewarning and alarm. Since the values are measured with measuring current transformers, the device is nearly independent of the load current and the nominal voltage of the system.
- Features
- Applications
- Accessories
- Ordering information
- Downloads
- AC/DC sensitive residual current monitor Type B acc. to IEC 62020 and IEC/TR 60755
- r.m.s. value measurement (AC+DC)
- Two separately adjustable response values 10…500 mA
- Frequency range 0…2000 Hz
- Start-up delay, response delay and delay on release
- Digital measured value display via LC display
- Measured value memory for operating value
- CT connection monitoring
- LEDs: Power On, Alarm 1, Alarm 2
- Internal/external test/reset button
- Two separate alarm relays (one changeover contact each)
- N/O or N/C operation and fault memory behaviour selectable
- Continuous self monitoring
- Multi-functional LC display
- Password protection for device settings
- Sealable transparent cover
- Two-module enclosure (36 mm)
- RoHS compliant
- Push-wire terminal (two terminals per connection)
- AC/DC sensitive residual current monitoring in earthed two, three or four conductor systems (TN and TT systems)
- Monitoring of variable-speed drives, UPS systems, construction site equipment, printing machines, battery systems, laboratory equipment, wood working machines, MF welding systems, furniture industry, medical electrical equipment, etc.
- AC/DC sensitive current monitoring of single conductors de-energised under normal conditions (e.g. N and PE conductors)
Optional accessories for LINETRAXX® RCMA420
Measuring current transformers
Connection cable measuring current transformer – RCMA420-D
Accessories
Type | Internal diameter (mm) | Art. No. |
---|---|---|
CTUB101-CTBC20 | ø 20 | B78120010 |
CTUB101-CTBC20P | ø 20 | B78120020 |
CTUB101-CTBC35 | ø 35 | B78120012 |
CTUB101-CTBC35P | ø 35 | B78120022 |
CTUB101-CTBC60 | ø 60 | B78120014 |
CTUB101-CTBC60P | ø 60 | B78120024 |
Connection cable measuring current transformer – RCMA420-D
Type | Length/m | Art. No. |
---|---|---|
CTX-100 | 1 | B98110080 |
CTX-250 | 2,5 | B98110081 |
CTX-500 | 5 | B98110082 |
CTX-1000 | 10 | B98110083 |
Accessories
Type | Art. No. |
---|---|
Mounting clip for XM420 enclosure | B98060008 |
Variants of LINETRAXX® RCMA420
Type | Response range IΔn | Frequency range | Supply voltage US* | Art. No.** |
---|---|---|---|---|
RCMA420-D-1 | 10…500 mA | 0…2000 Hz | DC 9,6…94 V / AC 16…72 V, 42…460 Hz | B74043001 B94043001 |
RCMA420-D-2 | 10…500 mA | 0…2000 Hz | DC 70…300 V / AC 70…300 V, 42…460 Hz | B74043002 B94043002 |
* Absolute values
**(B7… = push-wire terminal / B9… = screw-type terminal)
**(B7… = push-wire terminal / B9… = screw-type terminal)
Downloads for LINETRAXX® RCMA420
Category | Product | Language | Size | Download |
---|